MQ ENGINEERS LLC — Structural and civil engineering support

Insights

Curb ramp inspection: what to check and document

Curb ramps and pedestrian crossings are some of the most frequently built and most frequently rejected items on municipal road and sidewalk projects. A ramp can look finished and still fail acceptance because one slope is a fraction of a percent too steep, a landing is short, or a detectable warning panel is set in the wrong place. Problems found after the concrete cures are expensive to fix, because the usual fix is removal and replacement. A short, consistent inspection record before and after each pour protects the owner, the contractor and the inspector.

Start with the governing standard. Contract documents for public right-of-way work usually name the agency's standard details and the accessibility guidelines the agency follows. Read the project specification, the standard detail sheets and any approved shop drawings or ramp layout plans before the first pour. Note the ramp type for each corner (perpendicular, parallel or combination) and any location where the designer documented that full compliance was not technically feasible. That documentation, if it exists, belongs in the file before work starts, not after.

Check the forms before the pour. Measure the running slope of the ramp along the path of travel, the cross slope perpendicular to it, the slope and size of the landing or turning space, and the counter slope of the gutter where it meets the ramp. Under the 2010 ADA Standards, a ramp's running slope may not exceed 1:12 (8.33 percent) and its cross slope may not exceed 1:48 (about 2 percent); the project's adopted standard may set different or additional limits, and the contract governs. Confirm the width of the ramp and landing, the flush transition at the gutter with no lip, the location of drainage inlets so ponding does not occur at the bottom of the ramp, and the position of any poles, hydrants or signs that could block the clear path. Record the measurements and the tool used. A digital level or smart level should be checked against a known flat surface at the start of each day.

Watch the pour and finishing. Note the concrete delivery tickets, the mix identification, the time of placement and the weather. Confirm that detectable warning surfaces are the specified product and color, are set at the location shown on the detail, and are bedded flush. Finishing should not change the slopes that were checked on the forms; a quick re-measurement while the concrete is still workable is far cheaper than a later replacement.

Document the finished work. For each corner, take one wide photograph that shows the intersection and the ramp's location, and close photographs of the level readings on the ramp, landing and gutter. Use a file name that identifies the street, the corner and the date. Record the final measurements in the same table used for the form check, so a reviewer can compare before and after at a glance. Note any deficiency, who was told, and the agreed corrective action.

Close out cleanly. A ramp inspection file that holds the governing standard, the pre-pour measurements, the delivery tickets, the finished measurements and photographs, and the record of any correction is usually enough for an agency's acceptance review. It also gives the municipality a record it can use if the ramp is questioned later.